Crankcase pressure regulator Danfoss KVL 22 lut. 034L0045
Crankcase pressure regulator, suction line with copper solder connections, Schraeder valve for pressure testing.
|
Characteristic |
Value |
|
Type |
KVL 22 |
|
Factory setting |
2,00 bar |
|
Inlet connection type |
SOLDER, ODF |
|
Inlet size |
7/8" |
|
Inlet size |
22 mm |
|
Kv value [m³/h] |
14.09 |
|
Max. Test Pressure |
28,0 bar |
|
Max. Working Pressure |
18,0 bar |
|
Medium temperature range |
-45 - 105 °C |
|
Outlet connection type |
SOLDER, ODF |
|
Outlet size |
7/8" |
|
Outlet size |
22 mm |
|
Rated capacity R134a |
5,30 kW |
|
Rated capacity R22 |
7,10 kW |
|
Rated capacity R404A/R507 |
6,30 kW |
|
Rated capacity R407C |
6,50 kW |
|
Refrigerant(s) |
HCFC |
|
Refrigerant(s) |
HFC |
|
Regulating range |
0,2 - 6,0 bar |
Tech specs:
| Pictures: | illustrative |
| Manufacturer/responsible entity in the EU : | Danfoss Headquarters, Nordborgvej 81, 6430 Nordborg, Dania, danfoss@danfoss.com +45 7488 2222 ,
EVCO S.p.A. Via Feltre 81, 32036 Sedico (BL) ITALY phone +39 0437 8422 | fax +39 0437 83648 email info@evco.it | web www.evco.it ,
"Termo Plus sp. z o.o. Wilanowska 2, 05-509 Józefosław, Polska +48 15 687 49 91 biuro@esco.eu.com" |